P005046: Incomplete net

Cause

Possibility 1

Not all the connection points on a net were connected to one another.

Possibility 2

Two daisy chains of a net are not connected to one another.

Possibility 3

A connection was deleted within a net in the schematic. This creates a gap in the daisy chain. In this case, message P005047: Net definition point contains incomplete connections is also output.

Possibility 4

An additional connection that has not yet been assigned to a daisy chain was placed within a net in the schematic by copying. In this case, message P005050: Duplicate ID for net-based connections within a net (<x>) is also output.

Solution

Regarding option 1

Regarding option 2

Connect the two separated daisy chains.

Regarding option 3

You will find a detailed description in the Help under P005047: Net definition point contains incomplete connections.

Regarding option 4

You will find a detailed description in the Help under P005050: Duplicate ID for net-based connections within a net <x>.


Note:

EPLAN provides the possibility to automatically connect associated distributed terminals (menu items Options > Settings > Projects > "Project name" > Devices > Terminals > Settings (distributed terminals)), even if no drawn connections between the distributed terminals exist. However, this functionality is only effective if a net definition point determines the connections. At least one of the distributed terminal connection points occurring several times in the net so that the message "P005046: Incomplete net" is not output during configuring with distributed terminals.